088 setting up alarms in hmi (1)

因此,让我们看看设置数字警报涉及哪些其他媒体步骤,并在年龄之前记住它。
So let's see what other media steps involve in set up digital alarms and get it before age in mind.

好的。
OK.

现在您可能知道我已经告诉过您这些灯是由电脑内的宠物触发的。
Now you might know I have already told you that the lamps are triggered by a pet inside a PC.

好的。
OK.

因此,现在您可能在程序中拥有很多宠物,对于这些动物,您可能有 10 个警报或 100 个警报。
So now you might have a lot of pets in the program for the animals you may have maybe 10 alarms or maybe 100 alarms.

因此,在报警中的PC编程中的方法是分配一个空,例如在PNC中分配一个空。
So the approach in the PC programming in the alarm is to assign a void to assign a void in the PNC for example.

我会采取无效的M.W.
I would take void M.W.

100 兆瓦
100 M.W.

100 是我的话,你知道我会有 16 位。
100 is My Word which has you know that I would have 16 bits.

好的。
OK.

所以在这个词中我可以分配 16 个警报。
So in this word I can assign 16 alarms.

好的。
OK.

所以这个字专门用于报警位。
So this word is dedicated for the alarm bit.

然后你可以有另一个单词一对一,这将有 16 个以上的警报。
And then you can have you can have another word one to one which will have 16 more alarms.

好的,当您要在我重新定义的空白中的 h 中标记警钟时,这就是方法。
OK this is the approach when you are going to tag alarm bells in the h in my redefined the void.

这就是我在这里提到的。
That's what I mentioned here.

这些规格是警报器无效的标志。
The specs are a sign of void for the alarms.

让我们来谈谈 M.W.
So let's take a word M.W.

100百当前的例子。
100 hundred current example.

好的。
OK.

为此,需要在每个中设置警报,然后在 PC 中写入逻辑,并为特定警报信号触发该字的特定日期。
This is required by setting up an alarm in each then write the logic in PC and trigger a specific date for that word for a particular alarm signal.

我们已经在 PC 编程中看到了这一点,在 PC 编程中他们应该关闭这些电话。
This we have already seen in the PC programming that in the PC programming they should turn off those phones.

对于那个很抱歉。
Sorry about that.

主逻辑中的 PC 编程,如果您在其中看到此逻辑,我们只有两个位填充隔离墙和填充隔离墙,而我们在主逻辑中的其他位为九十九点一九十九点零,它们是四个用来给定时器供电,最后一点是危言耸听者和 100.0 和百比一。
The PC programming in the main logic if you see this logic inside this we have only two bits filling walled off and filling walls on and these other bits we have in the main logic here as ninety nine point one ninety nine point zero which are four they're used to energize a timer and the final bit for the alarmists and 100.0 and hundred to one.

这些是我们所拥有的最后部分。
These are the final bits which we are having.

因此,该位的无效值为 w 100。
So the void for this bit is and w 100.

好的,这个 vord 脚在演示文稿上有一个标志。
OK so this bit vord feet have a sign on the presentation.

MW

M.W.

百是这个词。
hundred is the word.

好的,贝茨维尔已经知道投注属于这个词。
OK so the Batesville already know the bets belongs to this word.

所以这是 Zambal 之一,如果你设置了 void M.W.
So this is one of the Zambal that if you set up the void M.W.

5.你必须用铲子。
5 you have to use it spade.

如果我 5.1 一份作为津贴,则 5.0 份。
And 5.0 if I 5.1 one for the allowance.

好的。
All right.

在我们的示例中,我们有单词“你饿了吗”,其赌注为 100.0 和百或 1。
In our example we have the word and are you hungry and it's bets are 100.0 and hundred or 1.

这将定义印度。
This will define India.

所以首先你必须以一种特定的方式来组织你的美丽逻辑,你有一个特定的词作为结尾,然后你使用它吐出公式。
So first you have to organize your beauty logic in a way that you have a specific word for the end and then you use it spits formula.

我会告诉你为什么用这个词。
I will tell you why you use this word.

因此,让我们在您的脑海中定义警报。
So let's define the alarms in over in your mind.

因此,我们只是说,在这里我将转到我的闹钟页面。
So for that we just say that here I will go to my page of my alarms.

这是我的 LA Mendo 离散 Alanzo 的图像,您正在谈论数字实验室,它也是路灯。
This is your image of my LA Mendo discrete Alanzo you are talking about digital labs which are also the streetlamps.

所以ID ID文本类触发触发投注。
So the ID ID text classes trigger trigger bet.

因此,我们首先要了解 ID ID 是特定于每个警报的,每个警报都有其自己的特定 ID。
So let's understand first the ID ID is specific to every alarm every alarm has its own specific IDs.

IDS 1 警报文本。
IDS 1 alarm text.

现在让我们看看误报全部饱和,即发生故障。
Now lets see the false alarm filling all saturated which is on failure.

我的感觉已经饱和了。
My feeling was saturated.

现在警报最后响起。
Now comes the alarm last.

什么是类,它有利于闹钟上的闹钟类,因为您将定义闹钟的行为。
What is a class and its good to alarm classes on the alarm clock as you will define the behavior of the alarm.

例如,这是我的第一个警报类,其显示名称作为一种解释标记,其名称为错误。
For example this is my first alarm class with the display name as a kind of explanation mark and its name is error.

现在错误是一个警报,但单模式确认意味着需要用户确认该警报已生成。
Now the error is an alarm but single mode acknowledgement it means it needs an acknowledgement from the user that this alarm has been generated.

用户应该知道它。
A user should know it.

这是警报。
This is the alarm.

否则,萨拉姆的批次就会消失,或者继续展示。
Otherwise the salaamed lot go or it keep on displaying.

好的,什么是未经确认而允许的警告。
OK and what is a warning which is allow without acknowledgement.

它不需要任何惩罚,因为这只是一个警告。
It doesn't need any punishment because this is just a warning.

这并不是任何有害的影响。
This is not any harmful effect.

这就像好的事情即将发生一样。
This is like OK something is going to happen.

所以这是没有承认的。
So this is without acknowledgement.

然后您会收到一些系统警报,这也是旧的确认不需要用户的任何确认。
Then you have some system alarms which is also that the old acknowledgement doesn't need any acknowledgement from the user.

你只要解决它,它就消失了。
You can just resolve it and it's gone.

然后你还有两节课本,但没有任何确认。
Then you have two more classes Ben and no acknowledgement.

再次与那个知识分子一起,无需承认,是否要使用它取决于您。
Again with that knowledge man and without acknowledgement it's up to you if you want to use it.

因此,我将在谨慎警报中使用警报类错误。
So I'm going to use the alarm class error in a discreet alarm.

默认情况下,这不是由我将在任务年龄死亡的街道触发的。
This is by default not triggered by the street that I'm going to die at the age of my task.

因此,如果我进入我的任务,我会创建一个单词标签,并将该标签与我的电脑的警报无效相关联。
So if I go to in my task I've created a tag which is word and I have linked this tag with the alarm void of my PC.

这是警报词。
Here is the alarm word.

这是来自 Pearcey 警报“我的电脑是什么”标签,即 M.W.
This is from the Pearcey alarm What is my PC tag which is M.W.

阅读我将其链接到我的蚀刻机我的闹钟闹钟世界。
read I link this to my etcher my alarm clock alarm world.

好的。
OK.

因此,在触发时间中,我将给出报警板的年龄,它实际上是 PC 类型的报警词。
So here in the trigger time I'm going to give the age of my alarm board which is actually a PC type alarm word.

大概有 100 个。
And probably 100.

默认情况下这是零,百老爹西多吐口水是零上的 100。
And this is zero by default hundred Dadds Sido the spit is 100 on zero.

这将触发消息感觉充满活力。
This is going to trigger the message feeling was animated.

所以,如果你看到这里和 100.0,这就是警报位的感觉,这是我自己的失败。
So if you see here and 100.0 this is feeling on the alarm bit which is my own failure.

正确的。
Right.

同样,DoubleClick 这个我也有另一个想法。
Similarly DoubleClick this one I have another idea too.

我将在这里只是复制这种感觉出现故障并与我的失败相比。
I will right here just copy this one feeling was malfunctioned and versus my off failure.

这是我的另一个 LAN,幸运的是我这里有 100 点,所以我有两条由 2 但 100.0 100 或 1 创建的警报消息。
This is my another LAN and this bit is by luck I have 100 dot one here so I have two alarm messages created by two but 100.0 100 or 1.

而这就是几百个。
And this is a few hundred.

这就是我们需要警报的原因,因为您在这里定义单词,然后他们在这里定义位。
So that's why we need an alarm would because you define the word here then they define the bits here.

如果你有另一个词,你可以在这里定义另一个词。
You going on to define another word here if you have another.

我们正在定义美。
We're defining the beauty.

好的。
OK.

现在我们在班级群里又看到了一件事。
Now there's one more thing we have seen the classes groups in the groups.

我在这个组中看到了一个组坦克,因为这是我的 IB 坦克,我可以将这两个警报分配在一个组中,这是我的,这是我的坦克,我只是从这里花时间。
You have a group tank I have seen in this group as this my IB one I can assign these two alarms in a group which is my Which is my tank and I just take time from here.

这不是分配给团体坦克的,我可以在这里给英雄时间。
This isn't assigned to the group tank and I can give the time here Heroes.

因此,如果我有其他警报(例如传送带),我可以将这些警报分类到组中的某个位置。
So if I have another alarms like conveyors I can categorize those alarms in the group somewhere.

因此,通过在组中定义警报来组织警报很容易,并且班级或两者都将得到确认。
So it's easy to organize your alarms by defining it in a group and the classes or both will have acknowledgement.

好的,这是我们在 Pearcey 上发出的谨慎警报,我们已经定义了类,我们已经定义了组,我们已经定义了单词和位。
OK this was the discreet alarm we have in over Pearcey and we have defined the class we have defined the group and we have defined the word and bits.

如果您对此有任何疑问,可以给我发表评论,我会回复您。
If you have any doubt up to here you can post me a comment and I'll get back to you.

回到你的演示,接下来是如何制作警报屏幕。
So going back to your presentation the next is how to make an alarm screen.

现在我稍后会回到那个地方,因为我想首先向您解释如何创建警报警报,因此请跳过这些步骤,因为这些步骤也会稍后出现。
Now I'll come back to that spot later because I want to first explain you how to create an alarm alarm so skip these steps because these steps will come later as well.

当过程超出安全范围时,我们有模拟警报和其他灯被触发。
We have analog alarms and other lamps are triggered when the process goes beyond the safety range.

安全意味着这是由用户定义的。
The safety means that this is defined by the user.

现在,例如在我们的坦克动画站区域中,我想在我的液位低于 20% 且我的液位高于 80% 时创建一些警报。
Now for example in our area in our tank animation stand here I want to create some alarms when my level is below 20 percent and my my level is above 80 percent.

好的。
OK.

所以在 80 以上和 20 以下我想生成一些警报。
So above 80 and below 20 I want to generate some alarms.

这是我的模拟警报,所以我将转到模拟警报。
This is my analog alarm so I'll go to analog alarms.

这又是我的一条警报短信。
Here it is again my one alarm text.

好的,让我们将此警报分为错误和警告。
Ok let's split this alarm's into errors and warnings.

好的。
OK.

例如,如果我的水平是或你可以看到你也可以在这里看到。
So for example if my level is or you can see you can also see here.

这在坦克屏幕上会更好。
That would be better on a tank screen.

如果我的等级在80以上90以下的话。
If my level is above 80 right and below 90.

好吧,假设 80 以上是我要达到的水平就很高了。
OK let's say above 80 be what I'm going to get to that level is high.

但如果它超过 90,则意味着它已经非常高了。
But if it goes above 90 then it means it's critically high.

因此,高于 80 时会产生警告,但如果高于 90 则会出现错误。
So above 80 be able to create a warning but if it goes above 90 will have an error.

让我们这样做吧。
Let's do that.

好的。
OK.

因此,在这种情况下,就进行了灯测试。
So in that case it reaches that here a lamp test.

正确的。
Right.

正确的。
Right.

等级。
Level.

你好。
Hi.

好的,这只是警告,因此类将警告此警告类,而无需确认。
OK this is just warning so classes will be warning this warning classes without acknowledgment.

我不必承认这一点。
I don't have to acknowledge it.

什么等级是高触发攻击。
What level is high trigger attack.

现在,标签正在监视关卡中发生的事情,并且关卡即将到来,您知道您可能会在哪里有该关卡,它会专心地到来。
Now the tag are monitoring what going on level and the level is coming where you know where you might have that level it's coming intently.

好的,这是一个 Tankleff 移动,它链接到我的 PC 级别。
OK this is a Tankleff move it is linked to is linked to my level of PC.

好的。
OK.

所以这里的触发标签将是我爸爸纠结的年龄。
So the trigger tag here will be the age of my dad tangling with.

好的。
All right.

我们正在监控直播。
We're monitoring the live.

因此,消息将被液位高触发,我将受到罐液位限制。
So message will be level high triggered I will be tank level limit.

极限是什么。
What is the limit.

所以我们的时间都集中在这里。
So here we have concentrated my time.

我会取一个常数,如果级别高于八,我会输入八。
I would take a constant and I would put eight the the level is above eight.

我们有直播消息。
We have the message live.

你好。
Hi.

这是更高的模式。
This is the higher mode.

是的。
Yeah.

你有一个较高的和一个较低的。
You have a higher and a lower.

这就是我的高端模式。
So this is my high end mode.

同样的下一个ID。
Similarly next ID.

现在在正确的水平上,临界高水平非常高。
Now on the right level critically high level is very high.

所以你应该小心。
So you should be careful.

在这种情况下,最后一次阿拉比警告会更好,因为我需要确认。
In this case that last Alabi warning it will be better because I need acknowledgment.

这是有害的。
This is harmful.

所以我在这里设置的限制是级别高于九级。
So and the limit I'll put it here is like the level is above nine.

然后会弹出显示或临界级别警告。
Then there will be a display pop up or a critical level warning.

同样,我将低三个级别。
Similarly I will do for three levels low.

对于低。
And for the low.

我会采取我会采取范围到两个对我来说是可以的。
I would take I would take a range to two is OK for me.

是的。
Yeah.

最小的下层和第 4 层确实在下面。
And the smallest lower and the 4 level really go below.

在这里,这又是一对一的,而且是低的。
And here again this is one to one and this is low.

这就是定义模拟余量的方式。
So this is how you define the analog allowance.

只需定义限制并定义标签并不困难。
It's not difficult you just define the limits and define your tag.

好的,那么您将收到有关设置模拟警报的这些消息。
OK then you would have these message messages Fluss about setting up an analog alarm.

那么让我们回到演示。
So let's go back to presentation.